Model Number | GTSI-5K0-3H | GTSI-6K6-3H | GTSI-10K-3H | GTSI-15K-3H | |
---|---|---|---|---|---|
PV String Input Data | Maximum PV Power at STC | 6.6 kWp | 8.8 kWp | 13.5 kWp | 20 kWp |
Recommended PV Power at STC | 5-6.6 kWp | 6.6-8.8 kWp | 10-13.5 kWp | 15-20 kWp | |
Absolute Maximum PV Voltage | 1000V | ||||
MPPT Voltage Range | 80-800V | ||||
MPTT Voltage Range for Full Load | 300-800V | 200-800V | 300-800V | 300-800V | |
StartUp Voltage | Settable(100-500V) | ||||
Input DC Voltage Nominal | 500V | ||||
Maximum continuous input current | 17A per string | ||||
PV Short Circuit Current | 20A per string | ||||
Number of MPPT Trackers | 1 | 2 | 3 | ||
Number of Input Strings per MPPT Tracker | 1 | ||||
MaximumBack-feed current | 0A | ||||
AC Output Data | Rated Output Power | 5kW | 6.6 kW | 10 kW | 15 kW |
Maximum Output Apparent Power | 6.6 kVA (@ maximum output voltage of 460V l-l) | 8.8 kVA (@ maximum output voltage of 460V l-l) | 13.5 kVA (@ maximum output voltage of 460V l-l) | 20 kVA (@ maximum output voltage of 460V l-l) | |
Nominal Output Voltage/Range | 415V/(350-460V) l-l | ||||
Nominal Output Frequency/ Range | 50 Hz/(47.5-52 Hz) | ||||
Maximum Continuous Output Current | 8.5 A per phase | 11 A per phase | 17 A per phase | 25 A per phase | |
In-rush current at inverter start-up | 15A (Peak) | ||||
Output Power Factor | Default is Unity (Adjustable from 0.8 leading to 0.8 lagging) | ||||
Output Current THD (@ Nominal output voltage and power) | <3% | <2.5% | <1.8% | <1.5% | |
Active Power Control | 0.5-5 kW with 0.1 kW resolution | 0.6-6.6 kW with 0.1 kW resolution | 1-10 kW with 0.1 kW resolution | 1.5-15 kW with 0.1 kW resolution | |
Reactive Power Control | 3 kVAr capacitive to 3 kVAr inductive | 4 kVAr capacitive to 4 kVAr inductive | 6 kVAr capacitive to 6 kVAr inductive | 9 kVAr capacitive to 9 kVAr inductive | |
Output Over Current Protection | 11A rms | 15A rms | 22A rms | 32A rms | |
Efficiency Data | Maximum Efficiency | 98.2% @ 720 | 98.3% @ 720V | 98.4% @ 720V | 98.4% @ 720V |
Data | Efficiency | PV Voltage and 2475 W solar power | PV Voltage @ 4950 W solar power | PV Voltage and 6 kW solar power | PV Voltage and 9.9kW solar power |
Efficiency @ Rated Power and rated PV and Grid Voltages | 98.1% | 98.2% | 98.2% | 98.2% | |
Euro Efficiency @ Rated PV and Grid Voltages | 97% | 97.3% | 97.5% | 97.5% | |
Euro Efficiency @ Rated Grid Voltage and Averaged over PV Voltage Range | 96.7% | 96.5% | 96.8% | 97.2% | |
Static MPPT Efficiency (EN50530 | 99.8% | ||||
Dynamic MPPT Efficiency (EN50530) | 98.6% | ||||
General Data | IP Protection | IP 65 | |||
Cooling | Natural Air Cooling | ||||
Operating Altitude | <=2000 m | ||||
Operating Temperature | -250C to 550C | ||||
Noise | Less than 25 dB | ||||
Humidity | 5% to 95% | ||||
Night Self consumption for control electronics | Less than 7W | ||||
Topology | Transformerless | ||||
Protective Class | Class I | ||||
Grid Side Connector | 5-pin connector, 650V, 25A, IP 68 | ||||
PV Side Connector | MC4 Connector, IP-67 | ||||
Weight | 16 kg | 20 kg | 25 kg | 29 kg | |
Dimensions | 300 (H) X 470 (W) X 180 (D) all in mm | 420 (H) X 404 (W) X 185 (D) all in mm | 490 (H) X 420 (W) X 185 (D) all in mm | 600 (H) X 420 (W) X 185 (D) all in mm | |
Protection | Anti-Islanding Protection | Integrated | |||
Input Reverse Polarity Protection | Integrated | ||||
SPD AC Side | 350 Vac, Type-III SPD Integrated | ||||
SPD DC Side | 1000 Vdc, Type-III SPD Integrated | ||||
Residual Current Monitoring Unit | Integrated | ||||
Output Over Current Protection | Integrated | ||||
Output Short Circuit Protection | Integrated | ||||
Grid Over Voltage Protection | Integrated | ||||
Standards | Safety Standard | IS 16221/IEC 62109-2 | |||
Anti-Islanding | IS 16169/IEC 62116 | ||||
Harmonic Current Control | IEC 61000-3-2 | ||||
Grid Under/Over Voltage Setting | As per CEA India | ||||
Grid Under/Over Frequency Setting | As per CEA India |